 AC-DC
40-100 Watts ECM Series
* * * * * * *
xppower.com
Compact Size - High Power Density Industrial & Medical Approvals Low Leakage Current Level B Conducted Emissions EN61000-3-2, -3 Compliant Convection-cooled Class II Approved 40-60 W Models
Specification
Input
* 90-264 VAC (120-370 VDC) * 47-63 Hz; 440 Hz * 40 W: 0.4 A max at 230 VAC 60 W: 0.6 A max at 230 VAC 100 W: 0.9 A max at 230 VAC Inrush Current * 40 A max at 230 VAC Earth Leakage Current * <125 A at 115 VAC/60 Hz <210 A at 230 VAC/50 Hz Input Protection * Internal 3.15 A fuse in line and neutral Input Voltage Input Frequency Input Current
General
Efficiency Isolation * 80-85% depending on model * 4000 VAC Input to Output 1500 VAC Input to Ground 500 VAC Output to Ground * 70 kHz typical * 60 W: 6.25 W/In3 100 W: 7.40 W/In3 * 250 kHrs per MIL-HDBK-217F
Switching Frequency Power Density MTBF
Environmental
Operating Temperature * 0 C to +70 C. Refer to derating curves for specific operating limitations. Cooling * Convection & fan-cooled ratings (see derating curves) Operating Humidity * 95% RH, non-condensing Storage Temperature * -20 C to +85 C Operating Altitude * 3000 m Shock * 30 g pk, half sine, 6 axes Vibration * 2 g rms, 5 Hz to 500 kHz, 3 axes
Output
* See tables * 5% on 3.3 V & 5 V versions, 10% on other single output models and V1 of multi-output models. See note 1 for ECM40/60 models Initial Set Accuracy * 1.0% V1, 5% V2, V3 & V4 Minimum Load * See tables Start Up Delay * 2 s max Start Up Rise Time * 50 ms Hold Up Time * 16/75 ms min at 115/230 VAC Line Regulation * 0.5% Load Regulation * 1% single output models; 3% V1, 5% V2 & V3 ECM40/60 multi-output models. 1% V1 & V2, 5% V3 & V4 ECM100 Cross Regulation * 2% on ECM40/60 only Over/Undershoot * None at turn on/off Transient Response * 4% max. deviation, recovery to within 1% in 500 s for a 25% load change Ripple & Noise * 1% pk-pk, 20 MHz bandwidth Overvoltage Protection * 115-135% Vnom, recycle input to reset Overload Protection * 110-150% on primary power limit, auto recovery Short Circuit Protection * Trip and restart (Hiccup mode) Temperature * 0.05%/C Coefficient Output Voltage Output Voltage Trim
EMC & Safety
Emissions Harmonic Currents Voltage Flicker ESD Immunity Radiated Immunity EFT/Burst Surge Conducted Immunity Dips & Interruptions * EN60601-1-2, EN61204-3, FCC 20780, EN55022 & EN55011, level B conducted * EN61000-3-2 * EN61000-3-3 * EN61000-4-2, level 2 Perf Criteria A * EN61000-4-3, 10 V/m Perf Criteria A * EN61000-4-4, level 3 Perf Criteria A * EN61000-4-5, level 3 Perf Criteria A * EN61000-4-6, 10 V Perf Criteria A * EN61000-4-11, 30% 10 ms, 60% 100 ms, 100% 5000 ms Perf Criteria A, B, B * EN60950, UL60950, CSA 22.2 601.1, EN60601-1, UL60601-1, CCC pending, contact sales
Safety Approvals
AC-DC
Models and Ratings
Max Power Output 1 Voltage +5.0 +7.0 +9.0 +12.0 +15.0 +18.0 +24.0 +33.0 +48.0 +5.0 +5.0 +5.0 +5.0 +5.0 +3.3 +5.0 V V V V V V V V V V V V V V V V Current Min/Max(3) 0.0 A/8.0 A 0.0 A/5.7 A 0.0 A/4.4 A 0.0 A/3.5 A 0.0 A/2.7 A 0.0 A/2.2 A 0.0 A/1.7 A 0.0 A/1.2 A 0.0 A/0.9 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A Voltage Output 2 Current Min/Max Voltage Output 3
ECM40
Current Min/Max Model Number(2) ECM40US05^ ECM40US07 ECM40US09^ ECM40US12^ ECM40US15^ ECM40US18 ECM40US24^ ECM40US33 ECM40US48^ ECM40UD21 ECM40UD22 ECM40UT31^ ECM40UT32 ECM40UT33^ ECM40UT34^ ECM40UT35
40 W
+12.0 +15.0 +12.0 +24.0 +15.0 +5.0 +3.3
V V V V V V V
0.1 0.1 0.1 0.1 0.1 0.1 0.1
A/2.0 A/1.5 A/2.0 A/1.0 A/1.5 A/1.5 A/1.5
A A A A A A A
-12.0 -12.0 -15.0 +12.0 +12.0
V V V V V
0.0 0.0 0.0 0.0 0.0
A/0.5 A/0.5 A/0.5 A/0.5 A/0.5
A A A A A
Notes
1. V2 will track a change in V1 by the same percentage change in voltage as V1 is trimmed. 2. To receive unit with cover fitted, add suffix `-C' to model number. For Class I operation only. 3. A 120% peak load can be taken for up to 100 ms with a 25% duty cycle. Average load not to exceed 40 W. Available from Farnell. See pages 204-206. ^ Available from Newark. See pages 207-208.
Mechanical Details
4.00 (101.6) 3.75 (95.25) 1.20 (30.5)
Input Connector J1 Pin 1 Line Pin 2 Neutral
1
J1 2
2.00 (50.8) 1.75 (44.45)
1
J1 mates with Molex housing 43061-0003 & Molex series 5194 crimp terminals Output Connector J2 Single Multi +V1 +V1 +V1 +V1 RTN RTN RTN RTN NC -V3 NC +V2
J2
6
V Adj. 4X o0.156 (3.96) mounting holes o0.312 (7.92) clearance top and bottom 0.14 (3.5) SMD component height
Pin 1 2 3 4 5 6
J2 mates with Molex housing 43061-0006 & Molex series 5194 crimp terminals Weight: approx. 0.33 lb (150 g)
Notes
1. All dimensions in inches (mm). Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25) 2. Cable harnessess with 300 mm wire available. For single output models, order part number ECM40/60S LOOM. For multi-output models, order part number ECM40/60DT LOOM. 3. Mating connector kit available. Order part number ECM40/60 CONKIT. 4. Covers available. Order part number ECM40/60 COVER^. Cover dimensions are 4.49 x 2.52 x 1.52 (114 x 64 x 38.5)
Derating Curves
All ECM40 models convection-cooled All ECM40 models with 5 CFM
Output Power
Output Power
100% 75% 50% 25% 0% 0 10 20 50 60 30 40 Ambient Temp (C) 70 80
100% 75% 50% 25% 0% 0 10 20 50 60 30 40 Ambient Temp (C) 70 80
Note: Derate by 10% if cover is fitted
Consult longform datasheet for installation information regarding optimum thermal ratings in convection-cooled applications.
AC-DC
Models and Ratings
Max Power Output 1 Voltage +5.0 +7.0 +9.0 +12.0 +15.0 +18.0 +20.0 +24.0 +33.0 +48.0 +5.0 +5.0 +5.0 +5.0 +5.0 +3.3 +5.0 V V V V V V V V V V V V V V V V V Current Min/Max(3) 0.0 A/12.00 A 0.0 A/8.60 A 0.0 A/6.70 A 0.0 A/5.00 A 0.0 A/4.00 A 0.0 A/3.30 A 0.0 A/3.00 A 0.0 A/2.50 A 0.0 A/1.80 A 0.0 A/1.25 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A Voltage Output 2 Current Min/Max Voltage Output 3
ECM60
Current Min/Max Model Number(2) ECM60US05^ ECM60US07 ECM60US09^ ECM60US12^ ECM60US15^ ECM60US18 ECM60US20 ECM60US24^ ECM60US33 ECM60US48^ ECM60UD21 ECM60UD22 ECM60UT31^ ECM60UT32 ECM60UT33^ ECM60UT34^ ECM60UT35
60 W
+12.0 +15.0 +12.0 +24.0 +15.0 +5.0 +3.3
V V V V V V V
0.1 0.1 0.1 0.1 0.1 0.1 0.1
A/3.0 A/2.5 A/3.0 A/1.5 A/2.5 A/1.5 A/1.5
A A A A A A A
-12.0 V -12.0 V -15.0 V +12.0 V +12.0 V
0.0 0.0 0.0 0.0 0.0
A/0.5 A/0.5 A/0.5 A/0.5 A/0.5
A A A A A
Notes
1. 2. 3. 4. V2 will track a change in V1 by the same percentage change in voltage as V1 is trimmed. To receive unit with cover fitted, add suffix `-C' to model number. For Class I operation only. A 120% peak load can be taken for up to 100 ms with a 25% duty cycle. Average load not to exceed 60 W. 48 V DC input version of 12 V single output model available in OEM quantities (DCM6048S12). Contact sales for details. ^ Available from Newark. See pages 207-208.
Available from Farnell. See pages 204-206.
Mechanical Details
4.00 (101.6) 3.75 (95.25) 1.20 (30.5)
Input Connector J1 Pin 1 Line Pin 2 Neutral J1 mates with Molex housing 43061-0003 & Molex series 5194 crimp terminals. Optional ground (0.25 faston) tab available, contact sales. Output Connector J2 Single Multi +V1 +V1 +V1 +V1 RTN RTN RTN RTN NC -V3 NC +V2
J1 2
1
2.00 (50.8) 1.75 (44.45)
1
J2
6
Pin 1 2 3 4 5 6
V Adj. 4X o0.156 (3.96) mounting holes o0.312 (7.92) clearance top and bottom 0.14 (3.5) SMD component height
J2 mates with Molex housing 43061-0006 & Molex series 5194 crimp terminals. Weight: approx. 0.33 lb (150 g)
Notes
1. All dimensions in inches (mm). Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25) 2. Cable harnesses with 300 mm wire available. For single output models, order part number ECM40/60S LOOM. For multi-output models, order part number ECM40/60DT LOOM. 3. Mating connector kit available. Order part number ECM40/60 CONKIT. 4. Covers available. Order part number ECM40/60 COVER^. Cover dimensions are 4.49 x 2.52 x 1.52 (114 x 64 x 38.5). 5. Selected single output models available in a 3" x 5" footprint for OEM quantities. Contact sales for details.
Derating Curves
All ECM60 models convection-cooled All ECM60 models with 5 CFM
Output Power
Output Power
100% 75% 50% 25% 0% 0 10 20 50 60 30 40 Ambient Temp (C) 70 80
100% 75% 50% 25% 0% 0 10 20 50 60 30 40 Ambient Temp (C) 70 80
Note: Derate by 10% if cover is fitted
Consult longform datasheet for installation information regarding optimum thermal ratings in convection-cooled applications.
AC-DC
Models and Ratings
Single Output Models
Output Voltage +3.3 V +5.0 V +7.0 V +9.0 V +12.0 V +15.0 V +18.0 V +24.0 V +33.0 V +48.0 V Minimum 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A Output 1 Current Voltage Min/Max +5.0 V 0.0 A/12.0 A +5.0 V 0.0 A/12.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +3.3 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +3.3 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A Output Current Maximum 15.0 A 15.0 A 11.4 A 8.8 A 7.5 A 6.0 A 5.0 A 4.1 A 3.0 A 2.1 A Output 2 Current Voltage Min/Max +12.0 V 0.0 A/3.0 A +15.0 V 0.0 A/3.0 A +12.0 V 0.0 A/3.0 A +24.0 V 0.0 A/2.0 A +15.0 V 0.0 A/3.0 A +5.0 V 0.0 A/5.0 A +3.3 V 0.0 A/5.0 A +12.0 V 0.0 A/3.0 A +15.0 V 0.0 A/3.0 A +3.3 V 0.1 A/5.0 A +5.0 V 0.1 A/5.0 A +24.0 V 0.1 A/2.0 A +24.0 V 0.1 A/2.0 A +12.0 V 0.1 A/3.0 A +15.0 V 0.1 A/3.0 A with 5 CFM Cooling 20.0 A 20.0 A 14.3 A 11.1 A 8.3 A 6.6 A 5.5 A 4.1 A 3.0 A 2.1 A
ECM100
Model Number(1,3) ECM100US03*^ ECM100US05*^ ECM100US07* ECM100US09* ECM100US12*^ ECM100US15*^ ECM100US18* ECM100US24*^ ECM100US33* ECM100US48*^
Multi Output Models
Output Power Convection Forced Air Cooled 5 CFM 80 W 100 W 80 W 100 W 75 W 100 W 80 W 100 W 80 W 100 W 65 W 100 W 70 W 100 W 80 W 100 W 70 W 100 W 65 W 100 W 60 W 100 W 80 W 100 W 80 W 100 W 80 W 100 W 80 W 100 W Output 3 Current Voltage Min/Max Output 4 Current Voltage Min/Max Model Number(1,3) ECM100UD21* ECM100UD22* ECM100UT31*^ ECM100UT32* ECM100UT33*^ ECM100UT34*^ ECM100UT35* ECM100UT36* ECM100UT37* ECM100UQ41* ECM100UQ42*^ ECM100UQ43*^ ECM100UQ44* ECM100UQ45*^ ECM100UQ46*
-12.0 -12.0 -15.0 +12.0 +12.0 -5.0 -5.0 +12.0 +12.0 +12.0 +15.0 -12.0 -15.0
V V V V V V V V V V V V V
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8
A A A A A A A A A A A A A
-12.0 -12.0 -12.0 -15.0 -5.0 -5.0
V V V V V V
0.0 0.0 0.0 0.0 0.0 0.0
A/0.5 A/0.5 A/0.5 A/0.5 A/0.5 A/0.5
A A A A A A
Notes
1. To receive unit with cover fitted, add suffix `-C' to model number. 2. Output 3 available with opposite polarity for OEM quantities. 3. `*' denotes ECM100 models are class I only, contact sales for class II. 4. 48 VDC input version of 12 V single output model available in OEM quantities (DCM10048S12). Available from Farnell. ^ Available from Newark. See pages 204-208. Input Connector J1 Pin 1 Line Pin 2 Neutral
J1 mates with Molex housing 43061-0003 and Molex series 5194 crimp terminals. Optional ground (0.25 faston) tab available.
1
Mechanical Details
Weight: approx. 0.4 lb (180g)
4.50 (114.3) 4.25 (107.95) 1.20 (30.5)
2.50 (63.5) 2.25 (57.15)
2
J1
1
J2
12
4X o0.156 [3.96] mounting holes o0.312 [7.92] clearance top and bottom
V Adj.
Cover dimensions are 4.98 x 3.01 x 1.54 (126.5 x 76.4 x 39.0)
0.14 [3.5] SMD component height
Pin 1 2 3 4 5 6 7 8 9 10 11 12
Output Connector J2 Single Multi +V1 +V1 +V1 +V1 +V1 +V1 +V1 +V1 V1 RTN RTN V1 RTN RTN V1 RTN RTN V1 RTN RTN NOT USED +V2 NOT USED +V2 NOT USED V3 NOT USED -V4
Notes
1. All dimensions in inches (mm). Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25) 2. Cable harnessess with 300 mm wire available. For single output models, order part number ECM100S LOOM. For multi-outputs, p/n ECM100DT LOOM.
J2 mates with Molex housing 43061-0012 and Molex series 5194 crimp terminals.
Derating Curves
All ECM100 single output models convection-cooled
Output Power (W)
100 80 60 40 20 0 0 10 20 50 60 30 40 Ambient Temp (C) 70 80
3. Mating connector kit available for single output models. Order part number ECM100S CONKIT. 4. Covers available. Order part number ECM100 COVER^. 5. Available in a 3" x 5" footprint for OEM quantities. Contact sales for details.
All ECM100 models with 5 CFM
Note: 1. Derate by 10% if cover is fitted. 2. For multi output convectioncooled operation above +50 C derate linearly to 50% at +70 C.
100%
Output Power
B C D
A
A B C D
US24-48 US12-18 US05 US03
75% 50% 25% 0% 0 10 20 50 60 30 40 Ambient Temp (C) 70 80
Consult longform datasheet for installation information regarding optimum thermal ratings in convection-cooled applications.
22-Oct-07


▲Up To Search▲   

 
Price & Availability of ECM100UT31

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X